Safety valve guide

Safety Valve Orifice Letters D to T: Areas and Selection

Every flanged safety valve built to API 526 carries an orifice letter. This is what the letters mean, how big each one is, and how to choose.

By Flammer Technologies engineering · Updated October 2026

What the letters are

API 526 standardises flanged steel safety valves so that valves from different makers are interchangeable. It defines fourteen orifice sizes, lettered D, E, F, G, H, J, K, L, M, N, P, Q, R and T from smallest to largest, and fixes the inlet and outlet flange sizes and the centre-to-face dimensions that go with each. A valve is described by its inlet size, orifice letter and outlet size, for example 2 J 3: a 2″ inlet, J orifice and 3″ outlet.

Effective area and actual area

Each letter has two areas, and mixing them up is the most common sizing error.

Always pair an effective area with the effective coefficient, or an actual area with the certified coefficient. Never take one from each.

Orifice table

LetterAPI 526 effective area (in²)API 526 effective area (mm²)Flammer 66 Series actual area (mm²)Typical inlet × outletFlammer max set pressure (bar g)
D0.1107186.51″ × 2″414
E0.196126176.01″ × 2″414
F0.307198240.61½″ × 2″345
G0.503325380.01½″ × 3″255
H0.785506568.41½″ × 3″190
J1.287830940.02″ × 3″186
K1.838118613523″ × 4″153
L2.853184121423″ × 4″103
M3.60232326424″ × 6″76
N4.34280032164″ × 6″69
P6.38411646554″ × 6″69
Q11.05712983536″ × 8″41
R16.0010323114906″ × 8″21
T26.0016774186208″ × 10″21

Larger orifices are limited to lower pressures because of the force on the disc and the flange ratings available in those sizes. Other inlet and outlet combinations exist for most letters.

How to choose the letter

  1. Calculate the required area for the worst-case relief flow, using the equation for your fluid from API 520 Part I.
  2. Pick the smallest letter whose area is at least the required area and whose pressure rating covers your set pressure.
  3. Check the rated capacity of that orifice against the required flow. A large margin is not a benefit: a heavily oversized valve can chatter, opening and closing rapidly and damaging its seat. If the next letter up is far too big, consider two smaller valves.
  4. Check the inlet pressure drop (normally no more than 3 % of set pressure) and the back pressure for the valve type you have chosen.

Worked example

Air at 50 °C must be relieved at 5000 kg/h by a conventional valve set at 10 bar g, with 10 % overpressure and no back pressure.

StepCalculationResult
Relieving pressure1000 × 1.10 + 101.3251201.3 kPa abs
Gas constant C (SI)0.03948 · √(1.40 × 0.83336)0.02703
Coefficient0.9 × 0.9750.8775
Required area5000 / (0.02703 × 0.8775 × 1201.3) × √(323.15 / 28.97)586 mm²
OrificeH gives 568.4 mm², too small; J gives 940 mm²J
Rated capacity of J940 / 586 × 50008021 kg/h

The required area falls just above an H orifice, so the J is needed and it has 60 % more capacity than required. This is a case where checking the relief load again, or splitting it between two valves, is worth a few minutes. The quick estimate on the safety valve sizing page reproduces these figures.

Small valves outside API 526

Threaded and small flanged valves for low flows, thermal relief and portable equipment are not covered by API 526. They often use smaller orifices such as B and C, and their areas differ between manufacturers. The Flammer 9 Series, for example, covers orifices B to G in sizes from ½″ to 3″. For these valves, always size on the manufacturer's actual areas.